Bussmann Solar PV Fuses

PV-10A10F

Bussmann Solar PV Fuses PV-A10 In Stock

Bussmann PV-10A10F photovoltaic fuse, 10 A at 1000 Vdc, 10 x 38 mm ferrule, gPV and UL 2579 with a 50 kA breaking capacity.

The PV-10A10F is a Bussmann photovoltaic fuse rated 1000 Vdc at 10 A in a 10 by 38 mm ferrule body. It is designed for the string protection of a solar installation, where the fault current is DC and the ambient temperature is high, so it carries the gPV class and meets UL 2579 and IEC 60269-6. A photovoltaic array cannot be switched off like a mains supply, and its fault current flows without a natural zero crossing, so the fuse must be specifically rated for the DC voltage and the low-overload conditions of a solar array; an AC branch fuse must never be substituted. The PV-A10 series covers 1 A to 20 A and is available in ferrule, bolt-fixing, PCB and in-line versions with crimp terminals, so a string can be protected in the combiner or at the module. It is normally fitted in a matched finger-safe holder such as the CHPV or an inline holder, and the fuse and holder are chosen as a pair. Size the fuse above the array current at the hot ambient and below the cable and module rating. Every fuse BeiLuo ships is factory-traceable and includes an import declaration, a certificate of origin and a RoHS compliance file, and mainstream ratings are held in stock.

FAE Professional Review

The PV-10A10F is the standard 10 by 38 mm string fuse, and the important detail is the gPV DC rating: a PV array has no zero crossing, so only a DC-rated fuse is safe. Pair it with the right finger-safe holder and size it with the ambient derating, and it protects the string reliably.
ParameterValue
Voltage1000 Vdc
Current10 A
StandardgPV / UL 2579
Body10 x 38 mm ferrule
Breaking Capacity50 kA

Application Circuits

Application

Solar string protection

Reference circuits and application schematics for Solar string protection are available from our FAE team.

Application

String combiners

Reference circuits and application schematics for String combiners are available from our FAE team.

Application

Residential inverters

Reference circuits and application schematics for Residential inverters are available from our FAE team.

Need a reference schematic or design review? Our FAE engineers can share verified circuits and layout guidance for this part.

Related Documents

Alternative Part Numbers

ModelPackageNoteAction
PV-100ANH1 NH blade PV fuse for higher-current combiners View

Complementary Part Numbers

ModelPackageNoteAction
170M7217 High-speed fuse for the inverter DC link View
LP-CC-6 Class CC fuse for the inverter control circuit View

Frequently Asked Questions

What is the PV-10A10F rated for?

It is rated 1000 Vdc at 10 A in a 10 by 38 mm ferrule body, to the gPV class and UL 2579, with a 50 kA breaking capacity.

Size it above the array current at the hot ambient.

Request the PV-10A10F for your project

Which holder fits this fuse?

Use a matched Bussmann holder such as the CHPV finger-safe holder or an inline holder with the correct voltage rating. The holder must be rated for the DC voltage of the array, not just the fuse.

Choose the fuse and holder as a pair.

View the solar PV range

Is the PV-10A10F genuine and in stock?

BeiLuo supplies factory-traceable PV fuses through Bussmann authorized channels, with import declaration, certificate of origin and RoHS files on every order. Mainstream ratings are normally in stock.

Request a sample to validate on the bench.

Request stock, sample or a quote